Tags: annealed, applicable requirements, astm specifications, cable configuration, code phase, configuration specifications, cross linked polyethylene, icea, insulation, mils, neutral conductor, neutrals, phase conductors, secondary distribution, secondary ud cable, tempers, three phase, underground service, volt, volts,
spec
9O4-543-1223, 8OO-997-2443, Fax: 9O4-543-1734, www.paigeeleclectric.com
P7328D
QUADRUPLEX 6OOV
SECONDARY UD
INSULATION: CROSS-LINKED
POLYETHYLENE XLP
CONDUCTORS: ALUMINUM
SCOPE:
Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts.
CONSTRUCTION:
Conductors are stranded, compressed 1350-H16/H26 aluminum insulated with vulcanized interlinked polyethylene. Neutrals
are triple yellow extruded stripe. Neutrals have sequential footage markers. Conductors are durably surface printed for identifi-
cation. Three phase conductors and one neutral conductor are cabled together to produce the quadruplex cabled together to
produce the quadruplex cable configuration.
SPECIFICATIONS:
Paige's quadruplex or paralleled 600 volt secondary UD cable meets or exceeds the following applicable ASTM specifications.
· B-231 Aluminum 1350 Conductors. Concentric-Lay-Stranded
· B-609 Aluminum 1350 Round Wire. Annealed and Intermediate Tempers, for Electrical Purposes.
· B-786 19 Wire Combination Unilay-Stranded Aluminum Conductors for Subsequent Insulation.
Paige's quadruplex 600 volt secondary UD cable meets or exceeds all applicable requirements of ICEA S-105-692 for cross-
linked polyethylene insulated conductors and UL Standard 854 for Type USE-2.
CODE PHASE CONDUCTOR NEUTRAL DIAMETER WEIGHT ALLOWABLE
WORD (mils) PER 1000 AMPACITANCE
Size Stranding Insulation Size Stranding Insulation Single Pase Complete Direct In Ducts
FOOT
(AWG) Thick (mils) (AWG) Thick (mils) Conductor Cable Burial
(lbs.)
QUADRUPLEX WITH YELLOW EXTRUDED STRIPE NEUTRAL
Tulsa 4 7 60 4 7 60 346 833 255 120 85
Dyke 2 403 973 342 155 115
Notre Dame 1/0 19 80 2 512 1236 534 200 150
Syracuse 2/0 1 19 555 1340 657 225 170
Wake Forest 4/0 90 2/0 80 653 1589 974 290 225
Slipperyrock 350 37 95 4/0 831 2006 1544 385 305
ħAmpacity 90°C conductor temperature 20°C ambient, RHO 90, 100% load factor for three conductor triplex with neutral carrying only unbalanced load.